Please use this identifier to cite or link to this item:
http://repository.ipb.ac.id/handle/123456789/76380| Title: | Koefisien Pindah Panas Keseluruhan Alat Penukar Panas Dalam Pendinginan Nokturnal |
| Authors: | Gunadnya, I.B.P. Abdullah, K. Tambunan, Armansyah Halomoan Purwanto, Y. Aris Oktaufik, M.A.M. |
| Issue Date: | Aug-2008 |
| Publisher: | Fakultas Teknologi Pertanian, Universitas Udayana, Denpasar |
| Abstract: | A series of field experiments have been conducted to estimate values of thermal parameters of a heat exchanger. such as over all heat heat transfer coefficient (U), number of transfer- units (NTU), and effectiveness (E), in a nocturnal cooling system accumulated experimental data showed that these parameters are proportional to the logarithmic relation to mass flow rate of water flowing into the heat exchanger. Empirical correlation developed for this purpose indicated that correlation coefficient of U was 0.76. The correlation function developed for cross-fow is applicable to predict outlet air temperature with an average error of 0.1 oC. |
| URI: | http://repository.ipb.ac.id/handle/123456789/76380 |
| ISSN: | 0853-6414 |
| Appears in Collections: | Mechanical & Biosystem Engineering |
Files in This Item:
| File | Size | Format | |
|---|---|---|---|
| Jurnal Agrotekno_YAP 2008.pdf | 2.58 MB | Adobe PDF | View/Open |
Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.